Used to protect photovoltaic systems against direct and indirect atmospheric discharges generated by lightning strikes. It is installed between the positive and negative terminals of the photovoltaic panels and the earth socket, ensuring the discharge of electrical overloads that are caused by lightning strikes near the installation site of photovoltaic systems. The plus and minus terminals of the string (string) of the str strings of the strings are connected to the plus and minus terminals of the arrester and the PE terminal to the ground wire.
Free pick up today
Free
Fast delivery in Europe
5-7 days
19.99€
Delivery with Raben Logistics
5-7 days
19.99€
Payment Methods:
'- Nominal voltage of the photovoltaic system: 1000V
- MCOV [UCPV] : 1170Vdc
- Maximum system discharge current (8/20 µs) [lmax] : 40kA
- Voltage protection level [UP]: ≤4.0kV
- Voltage protection level at 5kA [UP] : ≤ ≤3.5kV
- Integrated fuse breaking capacity/interrupting capacity: 30kV/1000Vdc
- Technology: overcurrent protection between short-circuit interruptions (SCI).
- Operating temperature range [TU]: -40℃ to 80℃
- Rated discharge current (8/20 µs) [(DC /DC-)> PE] [In] : 12.5kA
- Response time [tA]: <25ns
- Service/failure indication: green (good)/red (replacement)
- Conductor Ratings and Cross-Sectional Area: Minimum 60/70℃ 1.5mm²/14AWG Solid/Flexible and Maximum 60/70℃ 35mm²/2AWG Stranded/25mm²/4AWG Flexible
- Mounting: 35 mm DIN rail according to EN 60715
- Housing material: thermoplastic UL 94V0
- Degree of protection: IP20
- Capacity: 3 modules, DIN 43880
- IEC 6164311 Type 2, IEC 616431 Class II
Weight | 0,2 kg |
---|---|
Dimensions | 10 × 5 × 5 cm |
Type Current |